PIX with HVX CB upto 24kV, 2500A, 31.5kA – Outgoing

Schneider Electric PIX24-OG-H PIX with HVX CB upto 24kV, 2500A, 31.5kA – Outgoing

Product information
Key Features
- range of product PIX
- product or component type Incomer outcomer cubicle
- circuit breaker application Secondary main breaker
- network frequency 50/60 Hz
- [Ur] Rated voltage 0…24 kV
Schneider Electric
- Model #:
- PIX24-OG-H
- Part #:
- PIX24-OG-H
PIX24-OG-H Schneider Electric | BUY OR REPAIR
Overview
Medium Voltage Distribution and Grid Automation > Medium Voltage Switchgear > Primary Air Insulated Switchgear > PIX > PIX24-OG-H
Features
- range of product PIX
- product or component type Incomer outcomer cubicle
- circuit breaker application Secondary main breaker
- network frequency 50/60 Hz
- [Ur] Rated voltage 0…24 kV
- [Ud] Insulation voltage power frequency 50 kV 50 Hz 1 min
- [Up] Insulation voltage lightning impulse withstand 125 kV peak
- bus rated current 1250 A 2500 A
- [Ir] Rated current 630…2500 A
- [Ik] Short time withstand current 31.5 kA for 3 s
- internal arc classification Internal arc class AFLR
- internal arc protection 31.5 kA 1 s
- electrical connection Cable - 1 x 630...8 x 630 mm²bottom per phase
- product weight 800 kg 1200 kg
- height 2330 mm 2930 mm
- width 800 mm 1000 mm
- depth 1605 mm 1805 mm
- local signalling LED for presence of voltage
- standards IEC 62271-200
- device application Seismic
- type of installation Indoor installation
- additional device type Thermal sensor TH110 optional circuit breaker Thermal sensor TH110 optional busbar Thermal sensor TH110 optional cable Relay SEPAM Relay MiCOM Relay Easergy P3 Motor circuit breaker Motor DS optional Motor ES optional Power meter PowerLogic PM200 Power meter PowerLogic PM800 Power meter Eon
- arc fault detector option Yes - vamp (ordered separately)
- product destination Magelis HMI SMD without motor for remote withdrawability