MINIATURE CIRCUIT BREAKER – C60H – 1 POLE – 1 A – C CURVE

Schneider Electric A9N61501 MINIATURE CIRCUIT BREAKER – C60H – 1 POLE – 1 A – C CURVE

Product information

Key Features
  • range Acti 9
  • product name Acti 9 C60H-DC
  • product or component type Miniature circuit-breaker
  • device short name C60H-DC
  • device application Distribution
Schneider Electric
Model #:
A9N61501
Part #:
A9N61501
A9N61501 Schneider Electric | BUY OR REPAIR

    Need a Quote Sent?

    Repair Price Guarantee: We’ll meet or beat any competitor’s repair price.

    We are committed to your privacy. Global Electronic Services uses the information you provide to contact you about our relevant content, products, and services. You may unsubscribe from these communications at any time. For more information, please review our Privacy Policy.

    Overview

    Low Voltage Products and Systems > Electrical Protection and Control > Acti9 Devices for DC Circuits (Direct Currrent) > Acti9 C60H-DC, Acti9 C60PV-DC > A9N61501

    Features

    • range Acti 9
    • product name Acti 9 C60H-DC
    • product or component type Miniature circuit-breaker
    • device short name C60H-DC
    • device application Distribution
    • poles description 1P
    • number of protected poles 1
    • [In] rated current 1 A at 25 °C
    • network type DC
    • trip unit technology Thermal-magnetic
    • curve code C
    • breaking capacity 10 kA Icu at 220 V DC conforming to EN 60947-2 10 kA Icu at 220 V DC conforming to IEC 60947-2 6 kA Icu at 250 V DC conforming to EN 60947-2 6 kA Icu at 250 V DC conforming to IEC 60947-2 20 kA Icu at 110 V DC conforming to EN 60947-2 20 kA Icu at 110 V DC conforming to IEC 60947-2
    • utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
    • suitability for isolation Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2
    • network frequency 50/60 Hz
    • [Ue] rated operational voltage 250 V DC
    • [Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 - 110 V DC 15 kA 75 % conforming to IEC 60947-2 - 110 V DC 4.5 kA 75 % conforming to EN 60947-2 - 250 V DC 4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN 60947-2 - 220 V DC 7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC
    • [Ui] rated insulation voltage 500 V DC conforming to IEC 60947-2 500 V DC conforming to EN 60947-2
    • [Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2