GHA Circuit breaker cubicle – Double BusBar – up to 40,5kV 2500A 40kA

Schneider Electric GHA-CB-DBB GHA Circuit breaker cubicle – Double BusBar – up to 40,5kV 2500A 40kA

Product information

Key Features
  • range of product GHA
  • product or component type Incomer outcomer cubicle
  • circuit breaker application Secondary main breaker
  • network frequency 50/60 Hz
  • [Ur] Rated voltage 24 kV 36 kV 38 kV 40.5 kV
Schneider Electric
Model #:
GHA-CB-DBB
Part #:
GHA-CB-DBB
GHA-CB-DBB Schneider Electric | BUY OR REPAIR

    Need a Quote Sent?

    Repair Price Guarantee: We’ll meet or beat any competitor’s repair price.

    We are committed to your privacy. Global Electronic Services uses the information you provide to contact you about our relevant content, products, and services. You may unsubscribe from these communications at any time. For more information, please review our Privacy Policy.

    Overview

    Medium Voltage Distribution and Grid Automation > Medium Voltage Switchgear > Primary Gas Insulated Switchgear > GHA > GHA-CB-DBB

    Features

    • range of product GHA
    • product or component type Incomer outcomer cubicle
    • circuit breaker application Secondary main breaker
    • network frequency 50/60 Hz
    • [Ur] Rated voltage 24 kV 36 kV 38 kV 40.5 kV
    • [Ud] Insulation voltage power frequency 85 kV 50 Hz 1 min
    • [Up] Insulation voltage lightning impulse withstand 125 kV 170 kV 150 kV 185 kV
    • bus rated current 1250 A 2000 A 2500 A
    • peak current 63 kA 80 kA 100 kA
    • [Ir] Rated current 630 A 1250 A 2000 A 2500 A
    • [Ik] Short time withstand current 25 kA for 3 s 31.5 kA for 3 s 40 kA for 3 s
    • internal arc classification Internal arc class AFLR Internal arc class AFL
    • internal arc protection 40 kA 1 s
    • electrical connection Cable - 3 x 1000 mm²top per phase
    • product weight 900…1600 kg
    • height 2400 mm 2800 mm
    • width 600 mm 800 mm 900 mm
    • depth 1700 mm 2200 mm
    • local signalling LED for presence of voltage
    • standards IEC 62271-200
    • device application Railway
    • type of installation Indoor installation
    • additional device type Relay SEPAM Relay MiCOM Relay Easergy P3 Thermal sensor TH110 optional Motor circuit breaker Motor DS optional Motor ES optional Power meter optional
    • monitoring function Pressure monitoring IDIS
    • arc fault detector option Yes - vamp (ordered separately)
    • product destination Magelis HMI SMD