ACTI9 IC60 RCBO – 4P – 16 A – C CURVE – 6000A/6KA – 300 MA – AC TYPE
Schneider Electric A9D55416 ACTI9 IC60 RCBO – 4P – 16 A – C CURVE – 6000A/6KA – 300 MA – AC TYPE
Product information
Key Features
- range Acti 9
- product name Acti 9 iC60 RCBO
- product or component type Residual current breaker with overcurrent protection (RCBO)
- device short name IC60 RCBO
- device application Distribution
Schneider Electric
- Model #:
- A9D55416
- Part #:
- A9D55416
A9D55416 Schneider Electric | BUY OR REPAIR
Overview
Low Voltage Products and Systems > Electrical Protection and Control > Acti9 Residual Current Devices – RCDs > Acti9 iC60 RCBO (2P, 3P, 4P) > A9D55416
Features
- range Acti 9
- product name Acti 9 iC60 RCBO
- product or component type Residual current breaker with overcurrent protection (RCBO)
- device short name IC60 RCBO
- device application Distribution
- poles description 4P
- number of protected poles 4
- [In] rated current 16 A
- network type AC
- trip unit technology Thermal-magnetic
- curve code C
- earth-leakage sensitivity 300 mA
- earth-leakage protection time delay Instantaneous
- earth-leakage protection class Type AC
- breaking capacity 6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
- suitability for isolation No conforming to IEC 60947-1
- quality labels VDE KEMA-KEUR NF IMQ
- device location in system Outgoer
- network frequency 50 Hz
- [Ue] rated operational voltage 380...415 V AC 50 Hz
- magnetic tripping limit 5...10 x In
- residual current tripping technology Voltage independent