ACTI9 IC40 – MINIATURE CIRCUIT-BREAKER – 1P+N – 16A – C CURVE – 4500A/6KA

Schneider Electric A9P52616 ACTI9 IC40 – MINIATURE CIRCUIT-BREAKER – 1P+N – 16A – C CURVE – 4500A/6KA

Product information

Key Features
  • range Acti9
  • product name Acti9 iC40
  • product or component type Miniature circuit-breaker
  • device short name IC40
  • device application Distribution
Schneider Electric
Model #:
A9P52616
Part #:
A9P52616
A9P52616 Schneider Electric | BUY OR REPAIR

    Need a Quote Sent?

    Repair Price Guarantee: We’ll meet or beat any competitor’s repair price.

    We are committed to your privacy. Global Electronic Services uses the information you provide to contact you about our relevant content, products, and services. You may unsubscribe from these communications at any time. For more information, please review our Privacy Policy.

    Overview

    Low Voltage Products and Systems > Electrical Protection and Control > Acti9 Miniature Circuit Breakers – MCBs > Acti9 iC40 > A9P52616

    Features

    • range Acti9
    • product name Acti9 iC40
    • product or component type Miniature circuit-breaker
    • device short name IC40
    • device application Distribution
    • poles description 1P + N
    • number of protected poles 1
    • neutral position Left
    • [In] rated current 16 A
    • network type AC
    • trip unit technology Thermal-magnetic
    • curve code C
    • breaking capacity 6 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2 4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
    • suitability for isolation Yes conforming to EN/IEC 60947-2
    • quality labels KEMA IMQ
    • network frequency 50/60 Hz
    • [Ue] rated operational voltage 230 V AC 50/60 Hz
    • magnetic tripping limit 5...10 x In conforming to EN/IEC 60898-1 8 x In +/- 20 % conforming to EN/IEC 60947-2
    • [Ics] rated service breaking capacity 4500 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 4.5 kA 75 % x Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2
    • limitation class 3 conforming to EN/IEC 60898-1