Product information

Key Features
  • range TeSys
  • product name TeSys D
  • product or component type Contactor
  • device short name LC1D
  • contactor application Resistive load
Schneider Electric
Model #:
LC1DT25V7
Part #:
LC1DT25V7
LC1DT25V7 Schneider Electric | BUY OR REPAIR

    Need a Quote Sent?

    Price Guarantee: We’ll beat any competitor’s repair price by at least 10%.

    We do not share personal information of our customers with anyone.

    Overview

    Low Voltage Products and Systems > Motor Starters and Protection Components > Contactors and Reversing Contactors > TeSys D > LC1DT25V7

    Features

    • range TeSys
    • product name TeSys D
    • product or component type Contactor
    • device short name LC1D
    • contactor application Resistive load
    • utilisation category AC-1
    • poles description 4P
    • power pole contact composition 4 NO
    • [Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC
    • [Ie] rated operational current 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • control circuit type AC at 50/60 Hz
    • [Uc] control circuit voltage 400 V AC 50/60 Hz
    • auxiliary contact composition 1 NO + 1 NC
    • [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    • overvoltage category III
    • [Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit 25 A (at 60 °C) for power circuit
    • Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 250 A at 440 V for power circuit conforming to IEC 60947
    • rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
    • [Icw] rated short-time withstand current 30 A 40 °C - 10 min for power circuit 61 A 40 °C - 1 min for power circuit 105 A 40 °C - 10 s for power circuit 210 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit
    • associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 40 A gG at <= 690 V coordination type 1 for power circuit 25 A gG at <= 690 V coordination type 2 for power circuit
    • average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
    • [Ui] rated insulation voltage Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1
    • electrical durability 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
    • power dissipation per pole 1.56 W AC-1
    • Front cover With
    • mounting support Plate Rail
    • standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
    • product certifications UL BV CSA CCC GL DNV RINA LROS (Lloyds register of shipping) GOST
    • connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
    • tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    • operating time 4...19 ms opening 12...22 ms closing
    • safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    • mechanical durability 15 Mcycles
    • maximum operating rate 3600 cyc/h 60 °C
    • coil technology Without built-in suppressor module
    • inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C)
    • hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C)
    • heat dissipation 2…3 W at 50/60 Hz
    • auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
    Call for Help