TeSys D contactor – 4P(2 NO + 2 NC) – AC-1 – <= 440 V 80 A - 220 V DC coil
Schneider Electric LP1D65008MD TeSys D contactor – 4P(2 NO + 2 NC) – AC-1 – <= 440 V 80 A - 220 V DC coil
Product information
Key Features
- range TeSys
- product name TeSys D
- product or component type Contactor
- device short name LP1D
- contactor application Resistive load
Schneider Electric
- Model #:
- LP1D65008MD
- Part #:
- LP1D65008MD
LP1D65008MD Schneider Electric | BUY OR REPAIR
Overview
Low Voltage Products and Systems > Motor Starters and Protection Components > Contactors and Reversing Contactors > TeSys D > LP1D65008MD
Features
- range TeSys
- product name TeSys D
- product or component type Contactor
- device short name LP1D
- contactor application Resistive load
- utilisation category AC-1
- poles description 4P
- power pole contact composition 2 NO + 2 NC
- [Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC
- [Ie] rated operational current 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- [Uc] control circuit voltage 220 V DC
- coil type DC standard
- [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
- overvoltage category III
- [Ith] conventional free air thermal current 80 A (at 60 °C) for power circuit
- Irms rated making capacity 1000 A at 440 V for power circuit conforming to IEC 60947
- rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
- [Icw] rated short-time withstand current 110 A 40 °C - 10 min for power circuit 260 A 40 °C - 1 min for power circuit 520 A 40 °C - 10 s for power circuit 900 A 40 °C - 1 s for power circuit
- associated fuse rating 125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit
- average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- [Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified
- electrical durability 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
- power dissipation per pole 9.6 W AC-1
- Front cover Without
- mounting support Plate Rail
- standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
- product certifications BV CCC CSA DNV EAC GL LROS (Lloyds register of shipping) UL
- connections - terminals Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
- tightening torque Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm
- operating time 4...19 ms opening 12...26 ms closing
- safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
- mechanical durability 6 Mcycles
- maximum operating rate 3600 cyc/h 60 °C
- coil technology Built-in bidirectional peak limiting diode suppressor
- control circuit voltage limits 0.1...0.3 Uc (55 °C):drop-out DC 0.85...1.1 Uc (55 °C):operational DC
- time constant 75 ms
- inrush power in W 22 W at 20 °C
- hold-in power consumption in W 22 W at 20 °C