circuit breaker Compact NS1250H – Micrologic 2.0 A – 1250 A – 4 poles 4t
Schneider Electric 33259 circuit breaker Compact NS1250H – Micrologic 2.0 A – 1250 A – 4 poles 4t
Product information
Key Features
- range Compact
- product name Compact NS
- range of product NS630b...1600
- device short name Compact NS1250H
- product or component type Circuit breaker
Schneider Electric
- Model #:
- 33259
- Part #:
- 33259
33259 Schneider Electric | BUY OR REPAIR
Overview
Low Voltage Products and Systems > Circuit Breakers and Switches > Molded Case Circuit Breakers – MCCBs > ComPact NS > 33259
Features
- range Compact
- product name Compact NS
- range of product NS630b...1600
- device short name Compact NS1250H
- product or component type Circuit breaker
- device application Distribution
- poles description 4P
- protected poles description 4t
- neutral position Left
- (In) rated current up to 65 °C 1250 A at 50 °C
- [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
- network type AC
- network frequency 50/60 Hz
- suitability for isolation Yes conforming to IEC 60947-2
- utilisation category Category B
- [Icu] rated ultimate short-circuit breaking capacity 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
- trip unit name Micrologic 2.0 A
- trip unit technology Electronic
- trip unit protection functions LI
- control type Toggle Rotary handle
- Circuit breaker mounting mode Fixed
- [Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
- [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
- [Ics] rated service short-circuit breaking capacity 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
- mechanical durability 10000 cycles
- power losses 44 W