C120N – CIRCUIT BREAKER – 1P – 125A – D CURVE

Schneider Electric A9N18381 C120N – CIRCUIT BREAKER – 1P – 125A – D CURVE

Product information

Key Features
  • range of product C120
  • range Acti 9
  • product name C120
  • product or component type Miniature circuit-breaker
  • device short name C120N
Schneider Electric
Model #:
A9N18381
Part #:
A9N18381
A9N18381 Schneider Electric | BUY OR REPAIR
Product Type *

We do not share personal information of our customers with anyone.

Overview

Low Voltage Products and Systems > Electrical Protection and Control > Acti9 Miniature Circuit Breakers – MCBs > Acti9 C120 > A9N18381

Features

  • range of product C120
  • range Acti 9
  • product name C120
  • product or component type Miniature circuit-breaker
  • device short name C120N
  • device application Distribution
  • poles description 1P
  • number of protected poles 1
  • [In] rated current 125 A at 30 °C
  • network type AC
  • trip unit technology Thermal-magnetic
  • curve code D
  • breaking capacity 3 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12 V DC conforming to EN/IEC 60947-2 15 kA Icu at 125 V DC conforming to EN/IEC 60947-2 10 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1
  • suitability for isolation Yes conforming to IEC 60947-2
  • network frequency 50/60 Hz
  • [Ue] rated operational voltage 380...415 V AC 50/60 Hz 125 V DC <= 144 V DC 12 V DC 220...240 V AC 50/60 Hz 230...400 V AC 50/60 Hz 130 V AC 50/60 Hz 12 V AC 50/60 Hz
  • magnetic tripping limit 10...14 x In
  • [Ics] rated service breaking capacity 15 kA 75 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC 2.25 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - <= 144 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz 7500 A 75 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
  • limitation class 3 conforming to EN/IEC 60947-2
Call Now ButtonCall for Help